6. RKC COMMUNICATION
IMS01J02-E4
101
Continued from the previous page.
Event DI type selection
(Identifier: R1 to R4)
Event DI
corresponding
channel selection
(Identifier: E1 to E4)
Note
Setting data
Description
0
Input always OFF
Always ON at
“Reversal” selection
1
Event DI input
1 to 80
0: OFF
1: ON
2
Event DI logic output
1 to 80
0: OFF
1: ON
3
Event DO output
1 to 72
0: OFF
1: ON
4
PCP error code
0: Not provided
1: Provided
5
Temperature rise completion
0: Rise not complete
1: Rise completed
6 PID/AT
logical
OR
0: All PID
1: Any one is in AT
7
Alarm 1
1 to18
0: OFF
1: ON
8
Alarm 2
1 to18
0: OFF
1: ON
9
Burnout
1 to18
0: OFF
1: ON
10
Heater break alarm (HBA)
1 to18
0: OFF
1: ON
11
Control loop break alarm
(LBA)
1 to18
0: OFF
1: ON
12
AI alarm 1
1 to 36
0: OFF
1: ON
13
AI alarm 2
1 to 36
0: OFF
1: ON
14
TI alarm 1
1 to 36
0: OFF
1: ON
15
TI alarm 2
1 to 36
0: OFF
1: ON
16
TI burnout
1 to 36
0: OFF
1: ON
17 to 30
Not settable
Each contact status can be monitored by the following identifier.
Digital input (1 to 8)
→
Event DI contact input monitor (Identifier: L4)
Logic input (1 to 4)/Logic section
→
Event DI logic input monitor (Identifier: L5)
Logic input (1 to 8)
→
Event DI logic output monitor (Identifier: Q5)
For identifier L4, L5 and Q5, see
6.2 Communication Identifier List (P. 61)
.