6. RKC COMMUNICATION
IMS01J02-E4
67
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Initial setting mode
[H-PCP-J]
IN
1 R/W
U 0: Normal communication
Normal communication is
possible.
1: Extended communication
(Initialize setting mode)
a
Normal and initial setting
communication are
possible.
0
Memory area number
[H-TIO-
, H-CIO-A,
H-SIO-A]
ZA
1
R/W
U
1 to 8
1
Alarm interlock release
[H-TIO-
, H-CIO-A,
H-TI-
, H-AI-
]
AR
1
WO
U
1: Release (1 only)
Auto/Manual transfer
[H-TIO-
, H-CIO-A]
J1
1
R/W
U
0: Auto 1: Manual
Setting will be invalid in
ON/OFF control and
Heat/Cool control.
0
Manual output value
[H-TIO-
, H-CIO-A]
ON
6 R/W
C
5.0 to
105.0 %
Setting will be invalid in
ON/OFF control and
Heat/Cool control.
H-TIO-C/D [Z-1017 spec.]:
105.0 to 0.0 % (cool-side)
0.0 to
105.0 % (heat-side)
0.0
Temperature rise
completion range
[H-TIO-
, H-CIO-A]
HD
6
R/W
C
1 to 10
C or 1 to 20
F
10 or 20
b
a
If Extended communication (Initialize setting mode) is selected, the content of each identifier described
in the
6.3 Initial Settings [Extended Communications] (P. 77)
can be changed or selected.
When the control is started, it is impossible to change the settings to the Extended
communications (Initialize setting mode). For the change to the Extended
communications (Initialize setting mode), the control must be first stopped by the
“Control RUN/STOP transfer (Identifier: SR).”
b
TC/RTD input: 10
C or 20
F
Voltage/Current input, H-SIO-A: 10 % of display scale
Continued on the next page.