6. RKC COMMUNICATION
IMS01J02-E4
83
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Alarm 1 differential gap
[H-TIO-
, H-CIO-A,
H-SIO-A]
HA
6
R/W
U
0.00 to 10.00
of span
0.10
Alarm 2 differential gap
[H-TIO-
, H-CIO-A,
H-SIO-A]
HB
6
R/W
U
0.00 to 10.00
of span
0.10
Alarm 1 type selection
[H-TIO-
, H-CIO-A,
H-SIO-A]
XA
1 R/W
U 0: Process high alarm
1: Process low alarm
2: Deviation high alarm
3: Deviation low alarm
4: Deviation high/low alarm
5: Band alarm
6: No alarm function
The factory
set value
varies
depending
on the
specifications
when
ordering.
Alarm 2 type selection
[H-TIO-
, H-CIO-A,
H-SIO-A]
XB
1 R/W
U 0: Process high alarm
1: Process low alarm
2: Deviation high alarm
3: Deviation low alarm
4: Deviation high/low alarm
5: Band alarm
6: No alarm function
The factory
set value
varies
depending
on the
specifications
when
ordering.
Alarm 1 hold action
[H-TIO-
, H-CIO-A,
H-SIO-A]
WA
1 R/W
U 0: Not provided
1: Provided
2: Re-hold action
Re-hold action will be valid
in deviation alarm.
The factory
set value
varies
depending
on the
specifications
when
ordering.
Alarm 2 hold action
[H-TIO-
, H-CIO-A,
H-SIO-A]
WB
1 R/W
U 0: Not provided
1: Provided
2: Re-hold action
Re-hold action will be valid
in deviation alarm.
The factory
set value
varies
depending
on the
specifications
when
ordering.
Alarm 1 interlock
[H-TIO-
, H-CIO-A,
H-SIO-A]
LA
1
R/W
U
0: Not provided
1: Provided
0
Alarm 2 interlock
[H-TIO-
, H-CIO-A,
H-SIO-A]
LB
1
R/W
U
0: Not provided
1: Provided
0