52
Pub. No. 1290 - January 2010
RITE-HITE
®
Dual-Dok
®
Combined Lift & Leveler System Owner’s Manual
ELECTRICAL SCHEMATIC
M
G
1. REFER ALL INSTALLATION AND SERVICE TO
QUALIFIED PERSONNEL.
2. ALL INCOMING POWER (FROM DISCONNECT TO
CONTROL BOX) AND LEVELER MOTOR FIELD WIRING
TO BE MINIMUM #12GA. 60°/75°C COPPER WIRE,
INSULATED SUFFICIENTLY FOR INCOMING VOLTAGE.
3. ALL CONTROL FIELD WIRING TO BE MINIMUM
#16GA. 60°/75°C COPPER WIRE ONLY, INSULATED
SUFFICIENTLY FOR INCOMING VOLTAGE.
4. ALL INTERNAL CONTROL BOX WIRING TO BE
#16GA. MINIMUM, 90°C, RED COPPER WIRE UNLESS
OTHERWISE NOTED, INSULATED SUFFICEINTLY FOR
INCOMING VOLTAGE.
5. TORQUE REQUIREMENTS:
CONTACTOR: 8.9-22 LB-IN (MIN-MAX)
OVERLOAD RELAY: 16 LB-IN
GROUND TERMINAL: 35 LB-IN
TERMINAL BLOCK: 5.0-5.6 LB-IN (MIN-MAX)
8.
LEGEND:
6. LS1 THROUGH LS7 PROVIDED BY RITE-HITE WITH
DUAL-DOK.
(
NOTE:
SWITCHES SHOWN IN STORED AT DOCK HEIGHT
POSITION.)
*OPTIONAL LIMIT SWITCHES PROVIDED BY RITE-HITE
OR BY OTHERS
- LS8 PROVIDED BY RITE-HITE OR OTHERS FOR
OVERHEAD DOOR OPEN INTERLOCK.
- LS9 PROVIDED BY RITE-HITE OR OTHERS FOR GATE
CLOSED INTERFACE.
(
IMPORTANT:
REMOVE TERMINAL BLOCK JUMPER WHEN
INSTALLING LS8, LS9 AND GLT ITL RELAY).
7. FUSED DISCONNECT NOTES:
- FUSED DISCONNECT IS
OPTIONAL
FROM RITE-HITE
PRODUCTS CORPORATION. FUSED DISCONNECT MUST
BE INSTALLED PER LATEST EDITION OF UL508A AND NEC
REQUIREMENTS.
- A BRANCH CIRCUIT DISCONNECT SHALL BE
LOCATED WITHIN A 50 FT. RADIUS AND BE VISIBLE FROM
THE CONTROL BOX LOCATION. [REFERENCE LATEST
EDITION OF NEC, SECTION 430]
DENOTES WIRE NUT CONNECTION
DENOTES FIELD WIRES.
DENOTES MALE/FEMALE PLUG CONNECTION
DENOTES WIRE CONNECTIONS THRU
TERMINAL BLOCK.
X2(WH)
X1F(RD)
X3F(RD)
1.0A 250V
DUAL ELM TD
10FU1
DUAL ELM TD
6.0A 250V
11FU1
X1(RD)
X3(RD)
1L3
1L2
1L1
109
108
107
106
105
104
102
103
101
100
111
110
50VA
119
122
121
120
118
117
116
115
112
114
113
(X4)
(X3)
(X1)
24v.
120v.
120V SECONDARY
24V SECONDARY
200VA
(X2)
500
500
504
#14GA. MIN.,
GREEN
SEE NOTE 2
#12GA. MIN.,
90°C, BLACK,
COPPER WIRE
SEE NOTE 7
FUSED DISCONNECT
G
L3
L2
1FU3
1FU2
1L3
1L2
FROM CUSTOMER MAIN POWER & SAFETY PROTECTION DEVICE.
L1
1FU1
1L1
T3
T2
ONE LEVELER PER OVERLOAD PROTECTION DEVICE.
[REFERENCE LATEST EDITION OF NEC, SECTION 430]
1MCR
1OL
SEE NOTE 2
T1
(OPTIONAL)
2FU1
TRANSFORMER
PRIMARY FUSING
SEE TRANSFORMER DETAIL
FOR PRIMARY CONNECTIONS
SEE MOTOR DETAIL
FOR OVERLOAD SETTINGS
SEE MOTOR CONNECTION
DETAIL FOR MOTOR FIELD
CONNECTIONS
{
{
2FU2
SEE FUSE REPLACEMENT TABLE
DETAIL FOR FIELD POWER FUSING
INCOMING POWER:
220-240/3/60
380-415/3/50
440-480/3/60
575-600/3/60
NOTES:
{
FIGURE 33A - ELECTICAL SCHEMATIC
Содержание DUAL-DOK 2200
Страница 2: ...2 Pub No 1290 January 2010 RITE HITE Dual Dok Combined Lift Leveler System Owner s Manual NOTES...
Страница 61: ...Pub No 1290 January 2010 61 RITE HITE Dual Dok Combined Lift Leveler System Owner s Manual NOTES...
Страница 81: ...Pub No 1290 January 2010 81 RITE HITE Dual Dok Combined Lift Leveler System Owner s Manual NOTES...
Страница 82: ...82 Pub No 1290 January 2010 RITE HITE Dual Dok Combined Lift Leveler System Owner s Manual NOTES...
Страница 83: ...Pub No 1290 January 2010 83 RITE HITE Dual Dok Combined Lift Leveler System Owner s Manual NOTES...