FAMILY CONDENS IS - Programmable parameters
* Output not available at present. * The value is expressed on the display in rpm/100 (e.g. 3700 = 37) W
ARNING: certain default values may be dif
ferent from those shown in the table, owing to the update level of the card.
N°
PAR
PARAMETER DESCRIPTION
UNIT OF
MEASUREMENT
MIN
MAX
DEFAULT
(factory set)
PARAM
set
via SAT
1
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
1
2
INSIGNIFICANT PARAMETER
10 (10kW*)
16 (16kW)
20 (20kW*)
26 (25kW)
30 (30kW*)
34 (35kW)
50 (50kW*)
70 (70kW*)
26 (25kW)
34 (35kW)
3
DEGREE OF BUILDING INSULATION
min
5
20
5
10
DHW MODE
0 (OFF)
1 (instantaneous)
2 (not used)
3 (external storage tank with thermostat)
4 (external storage tank with probe)
5 (DS built-in storage tank)
6 (3S built-in storage tank)
3
11
MAXIMUM SET-POINT OF DHW CIRCUIT
°C
40
60
60
12
MAXIMUM SET-POINT OF DHW STORAGE TANK
°C
40
80
60
13
EXTERNAL STORAGE TANK DELIVERY TEMPERATURE
°C
50
85
80
14
EXTERNAL STORAGE TANK DELTA (ON)
°C
0
10
5
20
HEATING MODE
0 (OFF)
1 (ON)
2 (REMOTE PANEL + AREA VALVES)
3 (BAG
2
)
4 (NOT USED)
5 (NOT USED)
6 (BAG
2
MIX)
7 (NOT USED)
8 (NOT USED)
1
21
MAXIMUM HEATING SET-POINT
°C
40
80
80
22
MINIMUM HEATING SET-POINT
°C
20
39
20
23
MAXIMUM HEATING FAN SPEED
(Range Rated adjustment)
rpm
METHANE LPG
25kW 60(**) 60(**)
35kW 60(**) 59(**)
MAX
24
MINIMUM HEATING FAN SPEED
rpm
METHANE LPG
25kW 12(**) 19(**)
35kW 12(**) 19(**)
MIN
25
POSITIVE HEATING DIFFERENTIAL
°C
2
10
6
26
NEGATIVE HEATING DIFFERENTIAL
°C
2
10
6
28
DO NOT MODIFY THE PROGRAMMING
15
29
DO NOT MODIFY THE PROGRAMMING
5
30
DO NOT MODIFY THE PROGRAMMING
0
31
MAXIMUM HEATING SET-POINT 2CH (circuit 2)
°C
40
80
45
32
MINIMUM HEATING SET-POINT 2CH (circuit 2)
°C
20
39
25
40
TYPE OF DHW THERMOSTAT OPERATION
0 (OFF)
1 (AUTO)
2 (ON)
1
41
DHW Memory
0 (OFF)
1 (AUTO)
2 (ON)
1
42
H.T.C. FUNCTION
0 (OFF)
1 (AUTO)
1
43
HEATING MEMORY
0 (OFF)
1 (AUTO)
1
44
THERMOREGULATION FUNCTION
0 (OFF)
1 (AUTO)
1
45
THERMOREGULATION CURVE INCLINATION (OTC)
-
2.5
40
20
46
THERMOREGULATION FUNCTION 2CH
0 (OFF)
1 (AUTO)
1
47
THERMOREGULATION CURVE INCLINATION (OTC) 2CH
-
2.5
40
10
48
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
-
50
TOUCH & GO FUNCTION
0 (OFF)
1 (ON)
1
51
HEAT REQUEST TYPE CH1 (circuit 1)
-
0
1
0
52
HEAT REQUEST TYPE CH2 (circuit 2)
-
0
1
0
61
ANTIFREEZE FUNCTION DHW TEMP. (ON)
°C
0
10
4
62
HEATING FUNCTION DELIVERY TEMP. (ON)
°C
0
10
6
63
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
6
65
EXTERNAL PROBE REACTIVITY
0 (VERY FAST) 255 (VERY SLOW)
20
85
SEMI-AUTOMATIC CHARGE
0 (DISABLED)
1 (ENABLED)
0
86
PRESSURE OF SEMI-AUTOMATIC CHARGE (ON)
bar
0.4
1.0
0.6
87
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
0
90
VARIABLE SPEED PUMP
-
0
100
41
92
ENABLING OF POST-CIRCULATION FROM DHW TO HEATING
-
0
1
0
93
DURATION OF POST-CIRCULATION FROM DHW TO HEATING
-
1
255
5
94
PUMP IN CONTINUOUS MODE ON FIRST CIRCUIT
-
0
1
0
95
PUMP IN CONTINUOUS MODE ON SECOND CIRCUIT
-
0
1
0
Содержание Family Condens 2.5 - 3.5 IS
Страница 101: ...101 HRVATSKI Sl 10 Sl 11 A A A B Sl 3 Sl 4 Sl 5 Sl 6 Sl 7 Sl 8 Sl 9 A Sl 12 Sl 13 Sl 15 Sl 14 Sl 16 Sl 17 Sl 18...
Страница 143: ...143 13 1 c N OFF RESET DHW IS DHW S DHW IS FAMILY N OFF KIS...
Страница 144: ...144 FAMILY CONDENS KIS FAMILY CONDENS IS 2 IS DHW IS DHW DHW IS DHW DHW IS DHW S DHW IS S SERVICE IS DHW S DHW c...
Страница 145: ...145 10 11 A A A B 3 4 5 6 7 8 9 A 12 13 15 14 16 17 18...
Страница 151: ...151 15 OFF 8 ENERGY FOR LIFE ENTER ESCAPE 21 10 3 PROG CODE ENTER ENTER A ENTER ENTER A ENTER ESCAPE ENTER ESCAPE 21...
Страница 189: ...189 SRPSKI Sl 10 Sl 11 A A A B Sl 3 Sl 4 Sl 5 Sl 6 Sl 7 Sl 8 Sl 9 A Sl 12 Sl 13 Sl 15 Sl 14 Sl 16 Sl 17 Sl 18...