122
However, after a two-hour period,
this will change and the thermostat
will take as long as five minutes for
every degree F to change the dis-
play. Therefore, for example a rapid
change of five degrees in room tem-
perature will not be correctly indicat-
ed at the thermostat for (up to) 25
minutes. This is done to buffer the
thermostat against rapid and insignif-
icant swings in temperature caused
by briefly opening a door or window.
This operation prevents excessive
cycling of the thermostat and is a
feature used in all modern ther-
mostats.
COMMUNICATING THERMOSTATS
COMMUNICATING THER-
MOSTATS
The modulating furnace is capable of
communicating with a thermostat and
condenser to improve cooling and heat-
pump airflow, displaying active faults
and active furnace information at the
thermostat and improved diagnostics
and troubleshooting.
WIRING A FURNACE FOR
COMMUNICATIONS.
MAXIMUM COMMUNICATING WIRE
LENGTHS (1, 2, R & C)
Max Wire Length – Thermostat to
Furnace = 100 FT @ 18 AWG*
Max Wire Length – Furnace to
Condenser = 125 FT @ 18 AWG*
Notes:
1. When using twisted pairs, be sure the
wires connected to pins labeled “1”
(recommended wire color = green)
and “2” (recommended wire color =
yellow) are a twisted pair.
2. Wires may be solid or stranded.
3. *Wire gage smaller than 18 AWG is
not approved or recommended for
this application.
4. When using existing wire from a pre-
vious installation, be sure to trim the
tip of the wire back past the insulation
and strip a small amount of insulation
from the wire to expose clean new
copper for the communicating con-
nections. Fresh copper must be
exposed when making the communi-
cating connections or communications
may not be properly established.
Figures 96 through 97 below are wiring
diagrams for connecting the furnace to
an approved ClimateTalk communicat-
ing thermostat and approved Rheem or
Ruud communicating condenser.
The only approved configuration for
fully communicating systems is to install
dedicated wires directly from the fur-
nace to the thermostat and a separate
set of dedicated wires directly from the
furnace to the condenser. Note: The
only approved configuration for systems
with a communicating condenser
requires that four dedicated wires (1, 2,
R and C) be installed from the furnace
to the condenser.
TWO NOTES ABOUT COM-
MUNICATING THER-
MOSTATS
1. When power to the thermostat has
been reset and/or the batteries are
replaced, the thermostat will respond
quickly to changes in room tempera-
ture as indicated by the room tem-
perature displayed at the thermostat.
2. For dual-fuel systems, once the
thermostat has switched over to
auxiliary heat (e.g. gas heat), sub-
sequent heat calls may also
immediatel
y begin with auxiliary
heat regardless of the dual-fuel
changeover point and the actual
outdoor temperature or the differ-
ence between room temperatures
and setpoint. This is true as long
as the subsequent heat call is
within 12 minutes or less of end
of the previous heat call. The
actual time between heat calls
that will cause this operation
varies but should not exceed 12
minutes.
FIGURE 96
WIRING DIAGRAM – COMMUNICATING CONFIGURATION
A-1114-01
Содержание RGFE
Страница 92: ...92 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 93: ...93 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 94: ...94 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 95: ...95 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 96: ...96 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 97: ...97 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 98: ...98 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 99: ...99 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 101: ...101 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED when the inducer is energized at low ...
Страница 102: ...102 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 103: ...103 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 104: ...104 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 105: ...105 TABLE 21 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 106: ...106 FIGURE 83 WIRING DIAGRAM STEPPER MODULATING GAS VALVE FUEL CODE HA OR HB FURNACE MODEL IS RGFE RGGE ...
Страница 107: ...107 FIGURE 84 WIRING DIAGRAM SOLENOID CONTROLLED GAS VALVE FUEL CODE HG OR HH FURNACE MODEL RGGE RGFE RGJF ...