PULSAR MEASUREMENT
85
OPTIONS
DESCRIPTION
6 = Differential
Control
Relay will
energise
“
ON
” when a differential condition is in
effect and,
de-energise
“
OFF
” when the differential
conditions cease. Two setpoints are required,
Differential
control “
ON
”, (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3) and
Differential
control, “
OFF
” (P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4).
This allows the relay to be used to activate a device because
of a differential level, between two points e.g. operate a rake
on a screen.
The
third parameter
for each relay determines the
assignment
or
condition
of the relay, where required.
P212, P222, P232, P242, P252, 262 - Relay Alarm ID/Pump Group,
P211, 221, 231, 241, 251, 261 = 1, 2, 3 or 6
This parameter has no function and will not be displayed.
P211, 221, 231, 241, 251, 261 = 4 (Flush Valve)
If the relay is selected for Flush Valve/Pump, then this parameter is used to
determine to which pump the Flush function is assigned. Enter the
relay
number to which the assigned pump is connected
.
P211, 221, 231, 241, 251, 261 = 5 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign
the relay to the 0 =
Open
condition (increase level) or 1 =
Close
condition
(decrease level).
The
fourth parameter, fifth parameter
and
sixth parameter
are set to
determine the switch points, “
ON
” and “
OFF
” for the relay and where
required the order of start. See control function, table (P211, 221, 231) for
further information.
P213, P223, P233, P243, P253 Relay Setpoint 1
P211, 221, 231, 241, 251, 261 =1 (Time)
This parameter determines the “Time Period” that the relay will remain “ON”.
Relay Setpoints are entered in Minutes.
See the appropriate relay Function tables (
P211, 221, 231, 241, 251, 261
)
for further information.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...