ZENITH 140
INSTRUCTION MANUAL
104
P301 Switch Mode
When an external duty switch is used this can be connected via the digital
inputs and facilitate the selection of the duty device manually, thereby
overriding the duty programmed within the unit.
This parameter determines the type of switch in use.
OPTIONS
DESCRIPTION
0 = Standard (Default)
A standard switch, e.g., rotary switch, can be used
with one switch position and a digital input
required for each pump.
1 = Normal
To reduce the number of digital inputs used, for
manual duty selection, a binary switch can be
supplied. Max. No. of digital inputs required being
three.
P302 Override Delay
A digital input can be assigned to receive an input, which will override the
setpoints of the pumps and start or stop them, immediately after the expiry
of the Override Delay, dependent on the selected Digital Input
Function
P373, 376, 379,
382, 385, 388, 391 = 3 (Override “ON”)
or
4 (Override
“OFF”)
and providing the level is above the
Min. Override
(
P303
), when
Override “ON”
is selected.
Enter the required delay time in minutes.
P303 Min Override
Determines the minimum level required before an
Override Delay
(
P302
)
will be in effect when Digital Input
Function P373, 376, 379, 382, 385, 388,
391 = 3 (Override “ON”).
Enter the required level in
Measurement Units
(
P104
).
P304 Input Delay
This parameter determines the delay applied, from the time a device (relay)
is called to “run” and when the status of the digital input is recognised as a
valid input. If the digital input is used to detect a “running” signal this
parameter should be set to reflect the time it takes from the device being
calle
d to “run” to the input being in its operational status.
Enter the required time in seconds.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...