ZENITH 140
INSTRUCTION MANUAL
136
mA Failsafe
P840 mA Failsafe Mode
This parameter determines what happens to the mA output in the event of
the unit going into fail-safe mode. The
default
is to do the same as the
system fail-safe
(
P808
), but this can be overridden to force the mA output
to an independent fail-safe mode as follows:
OPTION
DESCRIPTION
0 = Default
mA output will fail as per
P808
1 = Hold
mA output will retain its last known value.
2 = Low
mA output will fail to its
low
condition.
3 = High
mA output will fail to its
high
condition.
P841 mA Allocation
By default, the mA output will be representative of the reading obtained, as
determined by the
Mode P100
. When
P100
=
5
(Volume)
the output can
be assigned to be representative of the
level
. This parameter is
automatically set to the correct default option when selecting the
Mode
P100
and
under normal circumstances will not require changing.
The options, dependant on the
value
entered for
Mode P100
, are as
follows:
OPTION
DESCRIPTION
1 = Auxiliary (Optional)
mA output relates to the optional auxiliary input
level
2 = Xducer 1 (Default)
mA output relates to Xducer 1
level
3 = Xducer 2
mA output relates to ducer 2
level
4 = Average level
mA output relates to the
average level
of two
points of measurement.
P100 = 4
5
–
Differential
mA output relates to the
differential
level of
two points of measurement.
P100 = 5
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...