ZENITH 140
INSTRUCTION MANUAL
80
PUMP DUTY
DESCRIPTION
5 = Duty backup and assist
First pump comes on, if it cannot cope, it goes
off and next pump comes on (duty backup). This
continues until the last pump comes on and if it
cannot cope the first pump comes back on to
assist the last pump (duty assist) if the level
continues to rise all other pumps will come on
(assist) in turn until the level decreases to the
pump off points. Each pump has its own
setpoints, (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3 & P2
1
4, 2
2
4,
2
3
4, 2
4
4, 2
5
4, 2
6
4).
6 = Service ratio duty assist
All pumps are used to assist each other (run at
the same time) and each pump has its own
setpoints (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3 & P2
1
4,
2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4). And a service ratio
setting. The third setpoint (P2
1
5, 2
2
5, 2
3
5, 2
4
5,
2
5
5, 2
6
5) is used to set the service ratio. Each
time a pump is required to start then the pump
with the least running hours (with respect to the
service ratio) is started (i.e. the setpoints are re-
assigned accordingly). For example, if two
pumps A and B have the service ratio set to 2
and 1 respectively, then pump A will operate for
twice as many hours as pump B.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...