P373, 376, 379, 382, 385, 388, 391 Function
This parameter will set the function of the digital Input.
OPTIONS
DESCRIPTION
1 = Device Fail
(Default Input 1 to 6)
Digital input is used to Fail, (put out of service), a
device connected to the relay specified in
P374,
377, 380, 383, 386, 389, 392 Assignment
2 = Duty
Digital input is used to select the device, (pump),
connected to the relay specified in
P374, 377,
380, 383, 386, 389, 392 Assignment
as the
current duty device (pump).
3 = Override “ON”
Digital input is used to provide a signal to activate
an
Override “ON”
condition of pumps as
determined by
P302 Override Delay,
P303 Min.
Override
and
P306 Override Level
.
4 = Override “OFF”
Digital input is used to provide a signal to activate
an
Override “OFF”
condition of pumps after the
expiry of the delay time as determined by
P302
Override Delay
.
5 = Reset.
Digital Input 7 only.
(Default Input 7)
Input is used to
Reset
all
Device Fail
conditions.
Alternatively, the
+/-
key can be used, whilst in
RUN, to
Reset
any
Device Fail.
P373, 376, 379, 382, 385, 388, 391 Function
This parameter will set the function of the digital Input.
OPTIONS
DESCRIPTION
0 = None (Default)
Digital Input is not assigned to any relay
1 = Relay 1
Digital input is assigned to Device connected to Relay 1.
2 = Relay 2
Digital input is assigned to Device connected to Relay 2.
3 = Relay 3
Digital input is assigned to Device connected to Relay 3.
4 = Relay 4
Digital input is assigned to Device connected to Relay 4.
5 = Relay 5
Digital input is assigned to Device connected to Relay 5.
6 = Relay 6
Digital input is assigned to Device connected to Relay 6.
7 = All
Digital input is assigned to All relays with a device
connected.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...