ZENITH 140
INSTRUCTION MANUAL
88
Miscellaneous
P210, 220, 230, 240, 250 = 4 (Miscellaneous)
When a relay is set to be a
miscellaneous relay
, the
second parameter
determines its
function
.
P211, 221, 231, 241, 251, 261
–
Relay Function
This function allows the relay to work in relation to a clock or a specific event
and will be set to activate in relation to Real Time.
OPTIONS
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Clock
Relay will
energise ON
at a specified time each day as set
in Relay Setpoint 1 (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3). And
turns
OFF
,
de-energises
, after the specified “On Time”
period as set in Relay Setpoint 2 (P2
1
4, 2
2
4, 2
3
4, 2
4
4,
2
5
4, 2
6
4)
2 = Totaliser
Relay will energise ON momentarily each time the
specified flow has passed as set in Relay setpoint 1 (P2
1
3,
2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3), this parameter sets the
multiplication factor which will be applied to the on-
board totaliser (P820) to determine the switch point of
the relay. E.g., if the totaliser is set to totalise in cubic
metres and the relay is required to provide a closure
every 10,000 litres Relay setpoint 1 would be set to 10.
Relay setpoint 2 (P2
1
4, 2
2
4, 2
3
4, 2
44
, 2
5
4, 2
6
4) can be
used to select the time the relay will remain closed in
seconds.
Important Notice
When using a Relay to control a device at a specified time of day ensure
that the Time P932 is set correctly. And if required, enable Daylight
Saving for the appropriate time difference P970
–
P979.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...