P107 Span
This parameter is the distance from the face of the transducer that is not
measurable and is pre-set to the minimum value dependant on the
Transducer
(
P101
) selected. It should not be set to less than this figure, but
can be increased, typically to ignore close in obstructions.
TRANSDUCER
NEAR BLANKING DISTANCE
P101 = dBMach3
Default blanking distance = 0.00 metres
P101 = dB3
Default blanking distance = 0.125 metres
P101 = dB6
Default blanking distance = 0.30 metres
P101 = dB10
Default blanking distance = 0.30 metres
P101 = dB15
Default blanking distance = 0.50 metres
P101 = dB25
Default blanking distance = 0.60 metres
P101 = dB40
Default blanking distance = 1.20 metres
P101 = dBS6
Default blanking distance = 0.20 metres
P101 = dBR16
Default blanking distance = *0.077 metres
P101 = dBR8
Default blanking distance = *0.077 metres
*The signal emanates from the curved face of the radar, but for the purposes
of measurement it is taken from the drip shield.
P108 Far Blanking Distance
This is the distance (as a percentage of the
empty level P105
) beyond the
empty point that the unit will be able to measure, and by default is pre-set
to 20% of the empty level.
If the surface being monitored can be extended beyond the
empty level
(
P105
) then the far blanking distance can be increased to a max. of 100% of
the empty level, provided it does not exceed the max range of the
transducer being used. This parameter is always entered as a % of the
empty level.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...