ZENITH 140
INSTRUCTION MANUAL
114
P515 Pump 1 Efficiency
This parameter displays the current value for Pump 1 Efficiency, which is
used to calculate the pump efficiency and will update with any change to the
Pump Draw Rate (P514)
.
P516 - P521 Pump 2
These parameters contain the same information as above for Pump 2.
P522 - P527 Pump 3
These parameters contain the same information as above for Pump 3.
P528 - P533 Pump 4
These parameters contain the same information as above for Pump 4.
P534 - P539 Pump 5
These parameters contain the same information as above for Pump 5.
Pumped Volume
Set Up
P205 Pump Vol. Enable
This parameter determines if Pumped Volume is in use or not.
OPTIONS
DESCRIPTION
0 = Off (Default)
Pumped volume calculation is switched
Off
1 = On
Pumped volume calculation is switched
On
P206 Settle Time
This parameter determines the time allowed for the level to settle after all
pumps have switched Off, to avoid any effects of flow back or turbulence,
before calculating the Inflow Rate. Enter desired time in minutes.
Default =
1 minute
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...