P812 Pump Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when a pump or general control
relay is switched on or off. The message is in the form “General 1 ON”, where
the number displayed is the number of the relay.
OPTION
DESCRIPTION
0 = No (Default)
Pump messages
will not
be displayed
1= Yes
Pump messages
will
be displayed
P813 Control Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when a control relay is switched
on or
off. The message is in the form “Time ON”.
OPTION
DESCRIPTION
0 = No (Default)
Control messages
will not
be displayed
1= Yes
Control messages
will
be displayed
P814 Miscellaneous Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when a miscellaneous relay is
switched on or off. The message is in the form “Clock ON”.
OPTION
DESCRIPTION
0 = No (Default)
Miscellaneous messages
will not
be displayed
1= Yes
Miscellaneous messages
will
be displayed
P815 Auxiliary Source
When
P100
=
4 (Average)
or
5
(Differential)
the auxiliary display line can
be used to display the
level
on any of the two points of measurement.
OPTION
DESCRIPTION
0 = Off (Default)
Auxiliary display not used to display
measurement readings.
1 = Auxiliary
Displays level from optional Aux input.
2 = Xducer 1
Displays level from transducer 1
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...