PULSAR MEASUREMENT
135
mA Limits
P836 mA Low Limit
This parameter sets the lowest level that the mA output will drop to, the
default is 0mA, but you can override this if the device you connect to cannot
for example accept less than 2mA, yet you want to use the 0-20mA range.
Default = 0.00mA
P837 mA High Limit
This parameter sets the highest level that the mA output will rise to, the
default is 20 mA, but you can override this if the device you connect to
cannot for example accept more than 18 mA, yet you want to use the 0-20
mA range.
Default = 20.00mA
mA Trim
P838 mA Low Trim
If the device you are connected to is not calibrated, and not showing the
correct
low value
(reading), then you can trim it using this parameter. You
can either type in the offset directly or use the arrow keys to move the
output up and down until you get the expected result (reading) on the
device that is connected.
P839 mA 1 High Trim
If the device you are connected to is not calibrated, and not showing the
correct
high value
(reading), then you can trim it using this parameter. You
can either type in the offset directly or use the arrow keys to move the
output up and down until you get the expected result (reading) on the
device that is connected.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...