Alarm relays, via the Quick Setup menu are entered as a % of span and are
as follows:
APPLICATION
NO. OF
PUMPS
PUMP NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Down
One
Pump 1
50%
20%
Pump Down
Two
Pump 1
Pump 2
50%
70%
20%
20%
Pump Down
Three
Pump 1
Pump 2
Pump 3
50%
60%
70%
20%
20%
20%
Pump Down
Four
Pump 1
Pump 2
Pump 3
Pump 4
40%
50%
60%
70%
20%
20%
20%
20%
Pump Down
Five
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
40%
50%
60%
70%
75%
20%
20%
20%
20%
20%
Pump Down
Six
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
40%
50%
60%
70%
75%
80%
20%
20%
20%
20%
20%
20%