IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 81 of 157
January 22, 2010
The gateway periodically sends all points configured for periodic/cyclic poll
(0x80000000) at the interval in milliseconds configured with the Cyclic Data
Transmission parameter:
You can also divide the monitored points into different groups, allowing the client to
periodically poll only certain points. This allows some points to be polled more
frequently than others.
Note:
You should configure the counter points (M_IT_NA) for general counter interrogation or group
counter interrogations.