Configure the Gateway
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 26 of 157
ProSoft Technology, Inc.
January 22, 2010
Use Recent
0
=
R
EPORT
M
ULTIPLE
,
1
=
R
EPORT
S
INGLE
This parameter determines how the events will be stored at the event queue and
reported to the remote Client. The 104S protocol supports event queues for each
data type that can store multiple, time-stamped events as they happen and report
those events to a remote Client. Some applications may require all events that
transpire be added to the queue and be reported. Other applications may require
only the most recent event of each IEC database point to be reported.
If this parameter is set to
0
-
R
EPORT
M
ULTIPLE
(the default), events for each
configured IEC monitor-type data point will be stored in a buffer. Each monitor point
data type has it's own unique buffer that can hold to 99 events. When the events are
reported to the remote Client, the buffer will be cleared and will begin to accumulate
new events as they happen, storing them until the next time they can be reported. If
the number of events that occur between reports exceed 99 for any given data type,
then the oldest event entry in the queue will be deleted to make room for the most
recent event. The advantage to this setting is that, with proper configuration, all
events will be captured and reported to the Client. The disadvantage is that the
event buffers can contain high volumes of data that will have to be transferred to the
Client.
If this parameter is set to
1
-
R
EPORT
S
INGLE
, only the most recent event for each
IEC database monitor point will be held in the buffer and reported to the Client. This
means that any events other than the most recent one for each point will not be
available. The advantage to this setting is that it limits the volume of event data that
may need to be transmitted to the Client to the total number of points of all types in
the IEC database. The disadvantage is that events for some points may be lost and
not reported to the Client.