IEC-60870-5-104 (104S) Protocol Implementation
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 92 of 157
ProSoft Technology, Inc.
January 22, 2010
And assume the Parameter Offets are configured as shown:
M_ME_NA Parameter Offset : 2400 #M_ME_NA IOA offset for parameter data
M_ME_NB Parameter Offset : 2500 #M_ME_NB IOA offset for parameter data
M_ME_NC Parameter Offset : 2600 #M_ME_NC IOA offset for parameter data
It would imply that the parameter points would be configured as follows:
M_ME_NA
Monitored Measured Normalized Point
Associated Parameter Point
400 2400
401 2401
402 2402
403 2403
… …
409 2409
In order to send a change of deadband for M_ME_NA Point 400, the client would
send a command type 110 to point 2400.
Содержание ProLinx 104S
Страница 4: ......