104S
♦
ProLinx Gateway
IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 93 of 157
January 22, 2010
M_ME_NB
Monitored Measured Normalized Point
Associated Parameter Point
500 2500
501 2501
502 2502
503 2503
… …
509 2509
In order to send a change of deadband for M_ME_NB Point 500, the client would
send a command type 110 to point 2500.
M_ME_NC
Monitored Measured Normalized Point
Associated Parameter Point
600 2600
601 2601
602 2602
603 2603
… …
609 2609
In order to send a change of deadband for M_ME_NC Point 600, the client would
send a command type 110 to point 2600.
3.6.2 Controlling the Generation of Events
Some applications may require that only some points should generate events. The
application will receive current values from points which have not been configured to
generate events only by issuing a poll request, or what the protocol specification
calls an
interrogation
. Other applications may require that all configured points
generate events.
The 104S gateway offers much flexibility for event control. You may control whether
or not events will be generated at three (3) different levels:
1
At the General Application Level (all configured points of all types)
2
At the Data Type Level (all configured point in each data type)
3
At the Individual Point Level (any specific point of any data type)