104S
♦
ProLinx Gateway
Configure the Gateway
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 37 of 157
January 22, 2010
2.13 [C_DC_NA_1
104]
This section defines the double point command database for the server emulated.
This information is sourced from the remote client and is transferred to the database.
You can associate a command with a monitored double point database value to
coordinate the command/monitor operation. You must enter the correct Monitor
Point # (IOA) and Monitor DB Addr values in the table. If the Require Select
parameter is not set to zero, a select command must be received before an execute
command will be processed.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Require
Select:
Each point is two bits and the DB Address value corresponds to the bit offset in the
gateway memory database. For additional information on how to set these
parameters, see the 104S Tutorial and Reference chapters of this manual.
2.14 [C_RC_NA_1
104]
This section defines the step command database for the server emulated. This
information is sourced from the remote client and is transferred to the database. The
control value can be associated with a monitored point as described in the previous
example.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Each point is one, 8-bit byte and the DB Address value corresponds to the byte
offset in the gateway memory database. For additional information on how to set
these parameters, see the 104S Tutorial and Reference chapters of this manual.