2.17 [C_SE_NB_1
104]
This section defines the scaled setpoint database for the server emulated. This
information is sourced from the remote client and is transferred to the database. You
can associate a command with a monitored scaled database value to coordinate the
command/monitor operation. You must enter the correct Monitor Point # (IOA) and
Monitor DB Addr values in the table. If the
Require Select
parameter is set to one (
1
)
or
Y
ES
, a Select command must be received from the Client before an execute
command from the Client will be processed.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Require
Select:
Each point is one, 16-bit word and the DB Address value corresponds to the word
offset in the gateway memory database. For additional information on how to set
these parameters, see the 104S Tutorial and Reference chapters of this manual.
2.18 [C_SE_NC_1
104]
This section defines the short-float setpoint database for the server emulated. This
information is sourced from the remote client and is transferred to the database. If
the
Require Select
parameter is set to one (
1
) or
Y
ES
, a Select command must be
received from the Client before an Execute command from the Client will be
processed.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Require
Select:
Each point is two, 16-bit words and the DB Address value corresponds to the
double-word offset in the gateway memory database. For additional information on
how to set these parameters, see the 104S Tutorial and Reference chapters of this
manual.