The SNTP driver will compute a new clock value every 5 minutes using the average
value of 10 samples each collected over an approximate 6-second period. This new
value will be used to adjust the clock maintained by the SNTP driver and used by the
application. If a valid database register is specified, the driver will place the time
value into the module's database. The first two registers will contain the number of
seconds and the next two registers will contain the number of microseconds since
January 1, 1970.
A list of some of the common NTP servers can be obtained at http://www.ntp.org/
or, http://support.ntp.org/bin/view/Servers/WebHome
Other server lists can be found by searching the World Wide Web for "NTP Servers".
NTP Server IP Address
Enter in dotted notation
This parameter sets the IP address of the NTP server to utilize for time acquisition.
Select an NTP server with the greatest accuracy that can be accessed all the time
from your network. Setting this IP address to 0.0.0.0 disables SNTP server requests.
Time Zone
-11 to 11
This parameter specifies the time zone offset to be used from the UTC time zone. A
value of zero uses UTC time. If the value entered is positive, the time zone is west of
the UTC time zone (that is, Eastern Standard Time is 5). If the value entered is
negative, the time zone is east of the UTC time zone (that is, Continental Europe is -
1).
Use Daylight Savings Time
Yes or No
This parameter specifies if daylight savings time will be used in the time
computation.