104S
♦
ProLinx Gateway
Configure the Gateway
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 27 of 157
January 22, 2010
2.2 [IEC-870-5-104
Database]
This section describes parameters in the [IEC-870-5-104 Database] section.
2.2.1 Short
Pulse
Time
0
to
2,147,483,647
(2 raised to the power of 31) milliseconds
This parameter defines the number of milliseconds to keep an IEC Command Point
set ON, HIGH, equal to one (1), before returning the point to OFF, LOW, equal to
zero (0), whenever a pulse point command is sent by the Client and the default value
of the
Default Command Qualifier
parameter is set to
S
HORT
.
2.2.2 Long Pulse Time
0
to
2,147,483,647
(2 raised to the power of 31) milliseconds
This parameter defines the number of milliseconds to keep an IEC Command Point
set ON, HIGH, equal to one (1), before returning the point to OFF, LOW, equal to
zero (0), whenever a pulse point command is sent by the Client and the default value
of the
Default Command Qualifier
parameter is set to
L
ONG
.