104S
♦
ProLinx Gateway
Configure the Gateway
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 29 of 157
January 22, 2010
M_SP_NA point count:
This parameter specifies the number of point values
assigned for the monitored single-point database. Range is 0 to 1000.
M_DP_NA point count:
This parameter specifies the number of point values
assigned for the monitored dual-point database. Range is 0 to 1000.
M_ST_NA point count:
This parameter specifies the number of point values
assigned for the monitored step-point database. Range is 0 to 1000.
M_BO_NA point count:
This parameter specifies the number of point values
assigned for the 32-bit bitstring database. Range is 0 to 1000.
M_ME_NA point count:
This parameter specifies the number of point values
assigned for the monitored normalized-point database. Range is 0 to 1000.
M_ME_NB point count:
This parameter specifies the number of point values
assigned for the monitored scaled-point database. Range is 0 to 1000.
M_ME_NC point count:
This parameter specifies the number of point values
assigned for the monitored scaled short-float point database. Range is 0 to 50.
M_IT_NA point count:
This parameter specifies the number of point values
assigned for the monitored counter-point database. Range is 0 to 1000.
C_SC_NA point count:
This parameter specifies the number of point values
assigned for the command single-point database. Range is 0 to 1000.
C_DC_NA point count:
This parameter specifies the number of point values
assigned for the command dual-point database. Range is 0 to 1000.
C_RC_NA point count:
This parameter specifies the number of point values
assigned for the command step-point database. Range is 0 to 1000.
C_BO_NA point count:
This parameter specifies the number of point values
assigned for the command 32-bit bitstring database. Range is 0 to 1000.
C_SE_NA point count:
This parameter specifies the number of point values
assigned for the command normalized-point database. Range is 0 to 1000.
C_SE_NB point count:
This parameter specifies the number of point values
assigned for the command scaled-point database. Range is 0 to 1000.
C_SE_NC point count:
This parameter specifies the number of point values
assigned for the command short-float point database. Range is 0 to 50.