IEC-60870-5-104 (104S) Protocol Implementation
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 62 of 157
ProSoft Technology, Inc.
January 22, 2010
M_SP_NA
A Monitored Single-Point occupies one binary bit and uses bit-addressing. For
example, if you configured the following points as shown:
The following table describes how these points would be stored in the gateway
memory database.
Inf. Object Address
Gateway Database Address
100
Bit 0 of word 100 (Bit address 1600)
101
Bit 1 of word 100 (Bit address 1601)
102
Bit 2 of word 100 (Bit address 1602)
Содержание ProLinx 104S