IEC-60870-5-104 (104S) Protocol Implementation
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 72 of 157
ProSoft Technology, Inc.
January 22, 2010
C_SC_NA
A Single-Point Command occupies one bit and uses bit-addressing. A Dual-Point
Command point occupies two bits and uses bit-addressing. For example, if you
configure the following points:
These points would be used as follows:
Inf. Object Address
Gate Database Address
800
Bit 0 of word 200 to hold the Control bit (Bit address
3200)
100
Bit 0 of word 100 to hold the associated Monitor Bit (Bit
address 1600. Must match the configuration of point 100
in M_SP_NA.)
801
Bit 1 of word 200 to hold the Control bit (Bit address
3201)
101
Bit 1 of word 100 to hold the associated Monitor Bit (Bit
address 1601. Must match the configuration of point 101
in M_SP_NA.)