Publication PSS-SG001A-EN-P – June 2005
Isysnet
9
Specialty I/O Module
PSSS23A
The PSSS23A serial-interface module offer a serial-link
communication interface solution for peripheral products with
RS-232 port.
The module allows a device with serial-interface output, i.e.,
bar code readers, to communicate up to 128 bytes of ASCII
data onto any network supported by Isysnet. Each module is
a single-channel, full-duplex interface and is rated for up to
38.4 kbaud. LED indicators on the module offer diagnostics
for the module, Isysnet PointBus backplane, and transmit/
receive status indication.
Isysnet ASCII Module Specifications
PSSS23A
Number of Serial Channels
1
Keyswitch Position
2 (Specialty)
PointBus Current (mA)
75
Power Dissipation
1.75 W @ 28.8VDC
Serial Port Parameters
Serial Character Framing
7N2, 7E1, 7O1, 8N2, *E1, 8O1, 7E2, 7O2
Serial Port Comm Speed
9600, 1200, 2400, 4800, 19.2 k, 38.4 k
Serial Port Receive from ASCII Device
Number of Receive Chars, Max
1...128
Receive Record Start Mode
No, exclude, include start delimiter
Receive Start Delimiter
ASCII character
Receive Record End Mode
No, exclude, include end delimiter
Receive End Delimiter
ASCII character
Send (Produce) on DeviceNet to Master
Receive String Data Type
Array, short-string, string
Pad Mode
Pad mode disabled, enabled
Pad Character
ASCII character
Receive Swap Mode
Disabled, 16-bit, 24-bit, 32-bit swap
DeviceNet Handshake Mode
Master/slave handshake, produce immediate
Produce Assembly Size
4...132
Serial Data Size
0...128 bytes
Receive Transaction ID
0...255
Serial Port Transmit to ASCII Device
Number of Transmit Chars, Max
1...128
Transmit End Delimiter Mode
No, exclude, include end delimiter
Transmit End Delimiter Character
ASCII
Consume on DeviceNet from Master
Consume String Data Type
Array, short-string, string
Transmit Swap Mode
Disabled, 16-bit, 24-bit, 32-bit swap
DeviceNet Record Header Mode
Transmit handshake/immediate
Consume Assembly Size
4...132
Serial Port Transmit/Explicit Messages from Configuration Tool
Transmit Serial Data String Size
0...128 bytes
Transmitted Serial Data Length
0...128 bytes
Transmit Transaction ID
0...255
Serial Port Status
TX FIFO overflow, RX FIFO overflow, RX parity error, handshake error, new data flag
Содержание H Series
Страница 135: ...DeviceNet Media Design and Installation Guide...
Страница 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Страница 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Страница 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Страница 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Страница 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Страница 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Страница 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Страница 263: ......
Страница 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Страница 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...