Identify Cable System Components
About Flat Cable
KwikLink flat cable is physically keyed to prevent wiring mishaps.
KwikLink cable is available in both heavy-duty and general purpose
versions. All variations of KwikLink cable are unshielded and contain four
conductors. Flat cable is used exclusively for the trunk line.
Class 1 (CL1) Heavy-duty Cable:
Per NEC specifications for a Class 1
circuit (see Appendix A), the power source must have a rated output of less
than 30V and 1000VA. Based on the size of the flat cable conductors, the
maximum current through the network must be no more than 8A. Class 1
KwikLink cable is UL listed for 600V and 8A at 24V dc. Use Class 1 drops in
conjunction with Class 1 flat cable.
Class 2 (CL2) Heavy-duty Cable:
More flexible than the CL1 cable, this
design adheres to NEC Article 725, which states that for a Class 2 circuit, the
power source must have a rated output of less than 30V and 100VA. In the
case of DeviceNet, running at 24V, the maximum allowable current is
100VA/24V or 4A. KwikLink CL2 cable is rated to 4A at 24V dc.
dc power pair 16 AWG
5.3 mm
(0.21 in.)
jacket material:
CL1: gray TPE
CL2: gray PVC
Auxiliary Power: black PVC
2.50 mm
(0.10 in.)
data pair 16 AWG
19.3 mm (0.76 in.)
blue & white pair:
CL1: data pair
CL2: data pair
Auxiliary Power: user
defined
30493-M
red
black
blue
white
Cl1 and Cl2 cables, Auxiliary power, the blue
and white pair, and red and black pair are used
in the manner shown here.
red & black pair:
CL1: power pair
CL2: power pair
Auxiliary Power: power
pair for outputs
side view
Class 1 (CL1) KwikLink Cable
Spool Size
Catalog Number
75 m (246 ft)
1485C-P1E75
200 m (656 ft)
1485C-P1E200
420 m (1378 ft)
1485C-P1E420
Class 2 (CL2) KwikLink Cable
Spool Size
Catalog Number
75 m (246 ft)
1485C-P1G75
200 m (656 ft)
1485C-P1G200
420 m (1378 ft)
1485C-P1G420
Содержание H Series
Страница 135: ...DeviceNet Media Design and Installation Guide...
Страница 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Страница 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Страница 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Страница 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Страница 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Страница 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Страница 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Страница 263: ......
Страница 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Страница 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...