Publication DNET-UM072C-EN-P - July 2004
4-18
Determine Power Requirements
Two Power supplies (not end-connected) in parallel with no V+
break
The following example uses the look-up method to determine the
configuration for two power supplies that are not end-connected. This
configuration provides the most power to the cable system. You must use
diodes at the power taps to prevent back-feeding of the power supplies. Check
your national and local codes for any restrictions on the use of parallel power
supplies.
1.
Determine the trunk line length of one end section (for this example we
will use section 3).
122m
2.
Add each device’s current together in section 3.
0.25+1.00+0.30 = 1.55A
power
supply
D3
PT
T
TR
TR
T
T
T
T
T
section 1
244 m
(800 ft)
122 m
(400 ft)
section 2
D2
D1
D4
D5
D6
30 m
(100 ft)
60 m
(200 ft)
122 m
(400 ft)
244 m
(800 ft)
0.25A
0.25A
0.25A
0.25A
1.5A
0.5A
TR = terminating resistor T = T-Port tap
PT = Power Tap D = device
31515-M
Содержание H Series
Страница 135: ...DeviceNet Media Design and Installation Guide...
Страница 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Страница 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Страница 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Страница 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Страница 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Страница 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Страница 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Страница 263: ......
Страница 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Страница 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...