Publication PSS-SG001A-EN-P – June 2005
Expansion Power Unit
The PSSSE24A expansion power unit passes 24VDC field
power to the I/O modules to the right of it. This unit extends
the backplane bus power and creates a new field voltage
partition segment for driving field devices for up to 13 I/O
modules. The expansion power unit separates field power
from I/O modules to the left of the unit, effectively providing
functional and logical partitioning for:
• Separating field power between input and output modules
• Separating field power to the analog and digital modules
• Grouping modules to perform a specific task or function
You can use multiple expansion power units with any of the
communication adapters to assemble a full system. If you are
using the PSSCDM12A adapter, you may use a PSSSE24A
expansion power unit to add additional modules. For example,
if you had a 36 module system with a PSSCDM12A adapter,
you would have at least two or more PSSSE24A expansion
power units to provide more PointBus current for modules to
the right of the supply.
• 24VDC to 5VDC converter
• 1.3A, 5VDC output (extend backplane power)
• Starts new voltage distribution
• Partitioning
1.3
1.0
0.5
Current
Voltage
10
19.2
Horizontal - 1 A @ (10-19.2V); 1.3 A @ (19.2-28.8V)
Vertical - 1 A @ (10-28.8V)
28.8
Isysnet
11
Power Distribution General Specifications
PSSSE24A
Power Supply Requirements
Note: In order to comply with CE Low Voltage Directives (LVD), you must use a
Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power
supply to power this adapter
Field Side Power Requirements
24VDC (+20% = 28.8VDC max.) @ 400 mA
Inrush Current, Max.
6 A for 10 ms
Input Overvoltage Protection
Reverse polarity protected
Power Supply Interruption Protection
Output voltage will stay within specifications when input drops out for 10 ms at
10V with max load
Power Supply Input Voltage, Nom.
24VDC
Operating Voltage Range
10…28.8VDC
Power Consumption, Max.
9.8 W @ 28.8VDC
Power Dissipation, Max.
3.0 W @ 28.8VDC
Thermal Dissipation, Max.
10.0 BTU/hr @ 28.8VDC
Isolation Voltage
1250V rms
Field Power Bus Supply Voltage, Nom.
12VDC or 24VDC
Field Power Bus Supply Current, Max.
10 A
PSSSE24A Current Derating for Mounting
Содержание H Series
Страница 135: ...DeviceNet Media Design and Installation Guide...
Страница 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Страница 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Страница 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Страница 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Страница 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Страница 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Страница 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Страница 263: ......
Страница 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Страница 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...