H Series Fieldbus 24 VDC Output Modules, Series A
E107P
7
Troubleshoot With the Indicators
PSST8M12A
I/O Status Indicators
Module Status Indicator
Network Status Indicator
PSST8M12A
24V dc Out
MOD
NET
0
1
0
1
2
3
4
5
6
7
2
3
4
5
6
7
Indication
Probable Cause
Network Status
Off
Device is not on line:
- Device has not completed
dup_MAC-id test.
- Device not powered - check module
status indicator.
Flashing Green
Device is on line but has no
connections in the established state.
Green
Device is on line and has
connections in the established state.
Flashing Red
One or more I/O connections in
timed-out state.
Red
Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
Flashing Red/Green Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identity Communication Faulted
Request - long protocol message.
Indication
Probable Cause
I/O Status
Off
Output is inactive
Yellow
Output is active and under control
Flashing Red
Open circuit detection. No load.
(Off-State only)
Red
Short circuit detected. (On-State only)
Indication
Probable Cause
Module Status
Off
No power applied to device
Green
Device operating normally
Flashing Green
Device needs commissioning due to
missing, incomplete, or incorrect
configuration
Flashing Red
Recoverable fault
Red
Unrecoverable fault -
may require device replacement
Flashing Red/Green Device is in self-test
If your RSLogic 5000 is Version 13.X:
• Choose the equivalent Rockwell Automation module from the list
of modules.
H Series Fieldbus
Modules
Equivalent Rockwell Automation
1738 ArmorPoint Modules
PSST8M8A
1738-OB8EM8
PSST8M12A
1738-OB8EM12
PSST8M23A
1738-OB8EM23*
* 1738-OB8EM23 profile will be available in RSLogix 5000 v15.
To use 1738-OB8EM23 in RSLogix 5000 v13, choose
1738-OB8EM12 profile and disable keying.
•
Enter a name (optional), slot number, and communication format.
Make sure to choose
Compatible Module for Electronic Keying
setting.
• Choose
Next to set RPI.
• Choose
Finish. Notice that the output module is now under the
I/O configuration
H Series Fieldbus
Modules
Equivalent Rockwell Automation
1738 ArmorPoint Modules
PSST16M23A
1738-OB16E19M23
PSST16D25A
1738-OB16E25DS
PSST16M12A
1738-OB16EM12
Содержание H Series
Страница 135: ...DeviceNet Media Design and Installation Guide...
Страница 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Страница 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Страница 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Страница 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Страница 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Страница 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Страница 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Страница 263: ......
Страница 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Страница 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...