Publication DNET-UM072C-EN-P - July 2004
Determine Power Requirements
4-9
Figure 4.6 Two End-Connected Power Supplies, KwikLink
Cable (Flat)
NEC/CE Code Maximum
Current Limit
∗
Exceeds NEC CL2/CECode 4A limit.
Length of trunk line, meters (feet)
C
ur
rent
(amp
er
es)
Network
length
m (ft)
Maximum
current (A)
0 (0)
8.00*
20 (66)
8.00*
40 (131)
8.00*
60 (197)
8.00*
80 (262)
8.00*
100 (328)
8.00*
120 (394)
8.00*
140 (459)
7.35*
160 (525)
6.43*
180 (591)
5.72*
200 (656)
5.16*
Network
length
m (ft)
Maximum
current (A)
220 (722)
4.69*
240 (787)
4.30*
260 (853)
3.97
280 (919)
3.69
300 (984)
3.44
320 (1050)
3.23
340 (1115)
3.04
360 (1181)
2.87
380 (1247)
2.72
400 (1312)
2.59
420 (1378)
2.46
41936
Содержание H Series
Страница 135: ...DeviceNet Media Design and Installation Guide...
Страница 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Страница 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Страница 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Страница 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Страница 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Страница 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Страница 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Страница 263: ......
Страница 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Страница 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...