Publication PSS-UM001A-EN-P – December 2016
2-12
What is the H Series Fieldbus DeviceNet Adapter?
Node Status Table Numeric Code Defi nitions
Numeric Code:
Text Message:
Defi nition:
Take this action:
82
Fragmentation Error
Error detected in sequence of
Check scan list table entry for slave
fragmented I/O messages
device to make sure that input and
from device.
output data lengths are correct.
Check slave device confi guration.
83
Slave Init Error
Slave device is returning error
Check accuracy of scan list table entry.
responses when scanner attempts
to communicate with it.
Check slave device confi guration. Slave
device might be in another master’s
scan
list.
Reboot slave device.
84
Not Yet Initialized
Adapter is initializing the
No action.
DeviceNet
channel.
85
Rcv Buffer Overfl ow
Data size is larger than 255 bytes.
Confi gure the device for a smaller
data
size.
86
Device Went Idle
Device is producing zero length data
Check device confi guration and slave
(idle state) while channel is in
node status.
Run
Mode.
89
ADR Failed
Failure occurred when downloading
Reconfi gure the ADR download data for
ADR data to the I/O module.
the I/O module.
91
Port Bus Off
Bus-off condition detected on
Check DeviceNet connections and
communications port.
physical media integrity.
Scanner is detecting communications
Check system for failed slave devices or
errors.
other possible sources of network
interference.
92
Port Power Off
No network power detected on
Provide network power.
communications
port.
Make sure that scanner drop cable is
providing network power to adapter
communications
port.
A user program can monitor the Device Failure Bit in the I/O
message(s) received from the adapter. When it has determined
the bit set, you can read the Faulted Node Table and Node Status
Table
,
using the Explicit Message Program Control Feature of the
scanner device, to determine the module experiencing problems
and the nature of those problems.
Chapter Summary and What’s Next
In this chapter you learned about the H Series
Fieldbus DeviceNet adapters. Move to Chapter 3 to
learn about using Auto Start Mode.
Содержание H Series
Страница 135: ...DeviceNet Media Design and Installation Guide...
Страница 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Страница 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Страница 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Страница 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Страница 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Страница 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...