Restriction on the number of passes of the heat exchanger hairpin
Minimum number of passes
= Number of steps × Distance between tube sheets × Number of rows × 1.5 ×10
-4
<For example>
Number of steps
12
Distance between tube sheets
1000 [mm]
:
:
:
Number of rows
3
Minimum number of passes = 12 × 1000 × 3 × 1.5 × 10
-4
= 5.4 < 6 passes