Automatic address setting using the remote controller
When the outdoor unit shown in “Basic wiring diagram 2” is used for group control of multiple units, use the remote
controller to perform automatic address setting. (During automatic address setting, “SETTING” blinks on the remote
controller display.)
Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
Main-sub remote controller control
Control using 2 remote controller
Main-sub remote controller control refers to the use of 2 remote controllers to control 1 or multiple indoor units.
(A maximum of 2 remote controllers can be connected.)
(1)
Example: (Outdoor) 1 - (Indoor) 1, 2
(Outdoor) 2 - (Indoor) 1, 2
So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that
the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB,
and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily
visible location on the indoor units (near the indoor unit nameplates).
(2) These numbers will be needed for maintenance.
Be sure to indicate them.
* Use the remote controller to check the addresses of the indoor units.
Press and hold the
Press the
For details, refer to the separate manual.
button again to return to the normal remote controller mode.
Then press the
(Each time the button is pressed, the address changes as follows: 1-1, 1-2, 2-1, 2-2, ....)
The indoor unit fan operates only at the selected indoor unit.
Confirm that correct fan is operating, and indicate the address on the indoor unit.
button and select the indoor address.
button and
button for 4 seconds or longer (simple settings mode).
Press the remote controller timer time
To select each refrigerant system individually and perform automatic address setting, press the remote controller
timer time
Then press either of the temperature setting
(Item code “A1” appears: Individual system automatic address setting)
Use either the
(R.C.1 is displayed.) Then press the
When automatic address setting for system 1 is completed, the system returns to normal stopped status.
Again press the remote controller timer time
Then in the same way as above (use the
automatic address setting.
button to display “R.C.2”), select the next system and perform
button and the
button simultaneously.
button. (Automatic address setting is performed for refrigerant system 1.)
button to select the outdoor unit to perform automatic address setting for.
or
buttons.
Then press the
(Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30.
When automatic address setting is completed, the units return to normal stopped status.)
button. (Item code “AA” appears: All systems automatic address setting.)
button and
button simultaneously. (Hold for 4 seconds or longer.)
button and
button simultaneously. (Hold for 4 seconds or longer.)
/
SM830231-02̲Single̲欧州.indb 298
SM830231-02̲Single̲欧州.indb 298
2014/09/19 13:21:48
2014/09/19 13:21:48
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...