Fig. 1-109
SELECTING THE LOCATION FOR THE INDOOR UNIT
5-1. Required Minimum Space for Installation and Service
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1.
2.
The indoor unit must be within a maintenance space.
The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
POSITION OF SUSPENSION BOLT
1 ~ 3mm
Drainage hole
Unit: mm
Remove the absorber at air
return hole before installation.
Absorber
A
TYPE
B
C
D
E
S-36PN1E5A
S-45PN1E5A
S-50PN1E5A
S-60PN1E5A
S-71PN1E5A
S-100PN1E5A
S-125PN1E5A
S-140PN1E5A
840
780
523
64
650
1060
1000
523
64
650
1260
1200
523
64
650
(Uint : mm)
Inspection hole
<Front>
Control box
Top view
Front view
(600 x 600)
600
600
1000
Above 250cm
A
B
C
D
E
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is decreased.
CAUTION
SM830231-02̲Single̲欧州.indb 382
SM830231-02̲Single̲欧州.indb 382
2014/09/19 13:22:03
2014/09/19 13:22:03
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...