Blower operation signal and protection signal
Power supply
SW1
X1 : Relay (field supply)
Limitation of AHU
When the AHU is selected, there are some limitations.
Cooling
Heating
Max.
Max.
-10
(DB)
(WB)
-20
(DB)
43
(WB)
15
(DB)
18
(DB)
16
(DB)
32
/ 23
(DB)
30
Outdoor temperature
Blower protect input
Blower signal output
Inlet air temperature
(to the heat exchanger)
Min.
Min.
Max.
Min.
The limitation of Heat exchanger volume, Air volume and Front area is shown in the following
Table 1-14, 1-15 and 1-16.
The limitation of temperature range is shown below.
Table 1-14 : Inside volume of heat exchanger
Table 1-15 : Air volume of heat exchanger
Table 1-16 : Front area of heat exchanger
Cooling Capacity
10 kW
12.5 kW
14 kW
0.51 m
2
0.51 m
2
0.51 m
2
0.43 m
2
0.43 m
2
0.43 m
2
Front area
1
2
3
4
X1
Minimum applicable load
DC 5 V, 1 mA
Maximum applicable load
AC 230 V, 2 A
SW 1 : operation command (field supply)
AC 220 ~240 V, 0.1 A
Max.
Min.
Cooling Capacity
10 kW
12.5 kW
14 kW
1980 m
3
/h 2100 m
3
/h 2160 m
3
/h
840 m
3
/h
1140 m
3
/h 1140 m
3
/h
Air volume
Max.
Min.
Cooling Capacity
10 kW
12.5 kW
14 kW
2.1 dm
3
2.1 dm
3
2.1 dm
3
1.7 dm
3
1.7 dm
3
1.7 dm
3
Heat exchanger
volume
SM830231-02̲Single̲欧州.indb 403
SM830231-02̲Single̲欧州.indb 403
2014/09/19 13:22:08
2014/09/19 13:22:08
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...