1
1-351
Others
(1) Checking After Installation
1)
Check that there are no gaps between the unit and
the ceiling panel, or between the ceiling panel and the
ceiling surface.
* Gaps may cause water leakage and condensation.
2)
Check that the wiring is securely connected.
* If it is not securely connected, the auto flap will not
operate.
(“P09” is displayed on the remote controller.)
In addition, the water leakage and condensation may
occur.
(2) Operating the Wireless Remote Controller
For details of installation, refer to the section “Wireless
Signal Receiver” in the supplied installation instructions.
(3) Selecting DC Fan Motor Tap (4-Way cassette)
Check the optional parts accordingly in the following
table.
Table for DC Fan Motor Tap Setting
Setting No.
Remote controller
setting data
Item code 5d
Contents &
optional parts name
(3)
0003
Air-blocking material
(for 3-way air discharge)
0003
Air-blocking material
(when a discharge duct is
connected)
(6)
0006
Air-blocking material
(for 2-way air discharge)
*1
When using optional parts in different setting No. in
combination with multiple units, conform it to the larger
setting No.
1)
When setting from the P.C. Board
<Procedure>
Stop the system before performing these steps.
Open the electrical component box cover, then
check the indoor unit control PCB.
Connect the jumper connector (2P: yellow)
which was supplied with the accessory to the
correct connector pin on the indoor unit control
PCB according to the setting number which was
confirmed in Table for DC Fan Motor Tap Settings.
Setting No. (3) :
Then connect the jumper connector to the
connector pin TP3 (2P: yellow) on the indoor unit
control PCB.
Setting No. (6) :
Then connect the jumper connector to the
connector pin TP6 (2P: white) on the indoor unit
control PCB.
2) When setting with the Wired Remote Controller
<Procedure>
Stop the system before performing these steps.
Press and hold the
,
and
buttons
simultaneously for 4 seconds or longer.
If group control is in effect, press the
button
and select the address (unit No.) of the indoor unit
to set. At this time, the fan at the indoor unit begins
operating.
Designate the item code
by adjusting the
Temperature Setting
/
buttons.
Press the timer time
/
buttons to select the
desired setting data.
* For item codes and setting data, refer to “Table for
DC Fan Motor Tap Setting”.
Press the
button.
(The display stops blinking and remains lit, and
setting is completed.)
*
If air-blocking material is used, use the same
procedure as in steps
–
above and change
the setting for item code “62” to “0000.”
If you wish to change the selected indoor unit,
follow the step
.
Press the
button to return to normal remote
controller display.
2
2
2
3
3
3
4
4
5
5
5
1
1
6
6
SM830231-02̲Single̲欧州.indb 351
SM830231-02̲Single̲欧州.indb 351
2014/09/19 13:21:55
2014/09/19 13:21:55
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...