4-3. Installing the Drain Pipe
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for the
drain and use the supplied hose band to prevent water
leaks.
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you to check
drainage. (Fig. 1-97)
Do not use adhesive tape at the drain connection port on
the indoor unit.
Insert the drain pipe until it contacts the socket, and then
secure it tightly with the hose band.
Do not use the supplied drain hose bent at a 90° angle.
(The maximum permissible bend is 45°.)
Tighten the hose clamps so their locking nuts face
upward. (Fig. 1-97)
Align the hose band with end of the hose, and
tighten so that it does not contact the bead.
Drainage check
section on drain port
(transparent)
Drain hose
(supplied)
Hard PVC
socket
VP-25
(not supplied)
Hard PVC pipe
VP-25
(not supplied)
Bead
Packing
(supplied)
PVC
adhesive
Fig. 1-97
(2) After connecting the drain pipe securely, wrap the supplied
packing and drain pipe insulator around the pipe, then
secure it with the vinyl clamps . (Fig. 1-98)
Drain insulator (supplied)
Vinyl clamps
(field supply)
1-98
.
g
i
F
N OT E
Make sure the drain pipe has a downward slant (1/100 or
more) and that there are no water traps.
Do not install an air bleeder as this may cause water to
spray from the drain pipe outlet. (Fig. 1-99)
Prohibited
Air bleeder
Fig. 1-99
If it is necessary to increase the height of the drain pipe, the
section directly after the connection port can be raised a
maximum of 500 mm. Do not raise it any higher than
500 mm, as this could result in water leaks. (Fig. 1-100)
300 mm or less
500 mm or less
Good
Fig. 1-100
Do not install the pipe with an upward slant from the
connection port. This will cause the drain water to flow
backward and leak when the unit is not operating.
(Fig. 1-101)
Upward slant
Prohibited
Fig. 1-101
Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be allowed to
hang unsupported from its connection to the unit. Fasten the
pipe to a wall, frame, or other support as close to the unit as
possible. (Fig. 1-02)
Support pieces
Fig. 1-102
Checking the Drainage
After wiring and drain piping are completed, use the following
procedure to check that the water will drain smoothly. For this,
prepare a bucket and wiping cloth to catch and wipe up spilled
water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Remove the tube cover and slowly pour about 1,200 cc
of water through the opening into the drain pan to check
drainage.
(3) Short-circuit the check pin (CHK) on the indoor control
circuit board and operate the drain pump. Check the water
flow through the transparent drain port and see if there is
any leakage.
Be careful since the fan will start when you short the pin on
the indoor control board.
(4) When the drainage check is complete, open the check pin
(CHK) and remount the insulator and drain cap onto the
drain inspection port.
Water intake
Fig. 1-103
CAUTION
CAUTION
CAUTION
SM830231-02̲Single̲欧州.indb 372
SM830231-02̲Single̲欧州.indb 372
2014/09/19 13:22:01
2014/09/19 13:22:01
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...