Table of Self-Diagnostic Functions and Corrections (Type K1)
Wired
remote
controller
display
(Field
supply)
Indoor unit
receiver lamp
Cause
Correction
Nothing is
displayed
Nothing is
displayed
Set the indoor operation switch ON.
E01
displayed
Operating lamp
is blinking.
E14
displayed
Connect the wiring correctly.
E06
displayed
E04
displayed
Standby lamp
is blinking.
1:1 connection (Single type)
Indoor operation switch is OFF.
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Indoor-outdoor inter-unit wiring is not
connected correctly.
——————
——————
Group connection
(Simultaneous multi system)
Same at left
Same at left
Remote control
communication wiring is cut
or is not connected correctly.
Same at left
Inter-unit control wiring is
cut or is not connected
correctly.
Turn ON the indoor unit power.
Check the inter-unit control wiring.
Perform automatic address setting
(See section “System Control” for Type K1.)
Refer to “System Control” for Type K1,
and make the correct settings.
Check the remote control communication
wiring.
Perform automatic address setting again.
E15
displayed
E16
displayed
L02
displayed
Both the
Operation lamp
and Standby
lamp are blinking
together.
——————
Indoor unit capacity is too low.
Indoor unit capacity is too high.
Indoor-outdoor unit type mismatch.
Same at left
Same at left
Check that the total capacities of the indoor
and outdoor units are appropriate.
Reverse 2 phases of the outdoor unit
3-phase power and connect them correctly.
P05
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
Same at left
Connect the units correctly.
Connect the units correctly.
Connect the units correctly.
L13
displayed
L04
displayed
Indoor-outdoor units are not setting
correctly.
Connect the units correctly.
Same at left
Same at left
Outdoor unit address is
duplicated.
displayed
L07
——————
Perform automatic address setting
(See section “System Control” for Type K1).
P15
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
No gas
Same at left
Check the refrigerant cycle (for gas leaks).
Remote control
communication wiring is
connected to the indoor unit,
however, it is set for
individual operation.
SM830231-02̲Single̲欧州.indb 303
SM830231-02̲Single̲欧州.indb 303
2014/09/19 13:21:48
2014/09/19 13:21:48
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...