E20 Connection Problem of Indoor/Outdoor Units
Error Detection Method
Error Diagnosis
The outdoor unit detects an error at following cases during auto address setting.
1.
2.
Indoor/outdoor control line is disconnected and also detects an error in the following cases when the outdoor unit is
turned On.
•
Address(es) of indoor unit(s) are not assigned correctly.
•
Capacity of indoor/outdoor units is mismatched.
•
Total number of indoor units is too many.
•
Indoor unit is not turned On.
•
Be sure that the indoor and outdoor units are connected with
correct combination written in catalog.
Are the address(es) of indoor unit(s) assigned correctly?
1-1
Are the indoor units turned on?
1-2
1-3
The indoor/outdoor control line may be disconnected somewhere between the indoor unit(s)
and the outdoor unit. Make sure the indoor/outdoor control line is connected.
1-4
1-2
Set its address
1-3
Power on
Yes
No
1 Indoor Unit
Yes
No
1-4
Correct the connection
Yes
No
SM830231-02̲Single̲欧州.indb 28
SM830231-02̲Single̲欧州.indb 28
2014/09/11 15:44:09
2014/09/11 15:44:09
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...