1
1-367
To unmount indoor unit
(1) Remove the screw cover on the bottom surface.
(Fig. 1-87)
(2) Fasten the frame to the rear panel using the 2 supplied
tapping screws 4 × 10 mm. (Fig. 1-87)
(3) Press the 2
marks on the lower part of the indoor unit
and unlatch the tabs. Then lift the indoor unit and unmount.
(Fig. 1-86)
N OT E
Under normal conditions, the installation design calls for a less
than 2 mm gap between the air conditioner unit and the wall.
Confirm that the gap is appropriate (less than 2 mm).
Drain Hose
a)
The drain hose should be slanted downward to the
outdoors. (Fig. 1-88)
b)
Never form a trap in the course of the hose.
c)
If the drain hose will run in the room, insulate the hose with
insulation* so that chilled condensation will not damage
furniture or floors. (Fig. 1-89)
*Foamed polyethylene or its equivalent is recommended.
WARNING
Do not supply power to the
unit or operate it until all
tubing and wiring to the
outside unit are completed.
Risk of Electric Shock
Fig. 1-86
Push
Screw
cover
Fig. 1-87
Fig. 1-88
Fig. 1-89
Screw
Slant
Drain
hose
Indoor
unit
Condensation
Insulation material
(Locally purchased)
must be used.
SM830231-02̲Single̲欧州.indb 367
SM830231-02̲Single̲欧州.indb 367
2014/09/19 13:22:00
2014/09/19 13:22:00
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...