1
1-397
Heat Insulation
Wall seal
Be sure to perform heat insulation on the drain,
liquid and gas piping.
Imperfection in heat insulation work leads
to water leakage.
CAUTION
(1) Use the heat insulation material for the refrigerant piping
which has an excellent heat-resistance (over 120°C).
(1) At this time, the refrigerant tubes (and electrical wiring
if local codes permit) should be taped together with
armoring tape in 1 bundle. To prevent condensation from
overflowing the drain pan, keep the drain hose separate
from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you
wrap the tubing, overlap half of each previous tape turn.
(3)
After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft
from entering. (Fig. 1-139)
Clamp the tubing bundle to the wall, using 1 clamp approx.
each meter. (Fig. 1-138)
N OT E
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also ensure that the condensation
drain hose splits away from the bundle and drips clear of the unit and the tubing.
(2) Precautions in high humidity circumstance.
This air conditioner has been tested according to the “JIS
Standard Conditions with Mist” and have been confirmed
that there are no faults. However, if it is operated for a long
time in high humid atmosphere (dew point temperature:
more than 23°C), water drops are liable to fall. In this case,
add heat insulation material according to the following
procedure:
Overlap with heat
insulator for piping.
Heat insulator
(Accessory)
Heat insulator for piping
(Local supply)
Band
(Accessory)
Indoor
unit
Fig. 1-136
Heat insulation material to be prepared… Adiabatic glass wool with thickness 10 to 20 mm.
Stick glass wool on all air conditioners that are located in ceiling atmosphere.
In addition to the normal heat insulation (thickness: more than 8 mm) for refrigerant piping (gas piping: thick piping)
and drain piping, add a further of 10 mm to 30 mm thickness material.
When the outdoor unit is installed on a higher position than
the indoor unit, install the trap so as not to instill rain water
into the wall by transmitting in piping.
Stuff the space among piping, the electric wire, and the drain
hose with putty and seal the penetration wall hole.
Make sure that rain water do not instill into the wall.
Drain pipe
Pipe down
Indoor
unit
Putty
Pipe
Trap
Incision
* Put the incision at the trap part of the heat insulator
(for water drain)
Fig. 1-137
6-8. Taping the Tubes
6-9. Finishing the Installation
Insulated tubes
Drain
hose
Clamp
Fig. 1-138
Apply putty here
Tubing
Fig. 1-139
SM830231-02̲Single̲欧州.indb 397
SM830231-02̲Single̲欧州.indb 397
2014/09/19 13:22:06
2014/09/19 13:22:06
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...