Table of Self-Diagnostic Functions and Corrections (Type K1)
Wired
remote
controller
display
Indoor unit
receiver lamp
Cause
Correction
Nothing is
displayed
Nothing is
displayed.
Connect the remote controller correctly.
E01
displayed
Operation lamp is
blinking.
Group connection and simultaneous-operation
multi system
Remote controller is not connected with indoor unit
correctly.
Automatic address setting has not been completed.
Inter-unit control wiring is cut or is not connected
correctly.
Remote controller is not connected with indoor unit
correctly.
Indoor unit power is not ON.
Turn ON the indoor unit power.
Check the remote controller and inter-unit control wiring.
Perform automatic address setting.
(See section “Automatic Address Setting” for Type K1
(for Link Wiring).).
E02
displayed
Remote controller is not connected with indoor unit
correctly.
Connect the remote controller correctly.
E14
displayed
Connect the wiring correctly.
E06
displayed
E04
displayed
Standby lamp is
blinking.
Remote control communication wiring is cut or is not
connected correctly.
Indoor-outdoor inter-unit wiring is not connected
correctly.
Inter-unit control wiring is cut or is not connected
correctly.
See section “Basic wiring diagram” for Type K1
(for Link Wiring).
Basic wiring diagram, and make thecorrect setting.
Check the remote control communication wiring.
Perform automatic address setting again.
E15
displayed
E16
displayed
P09
displayed
Timer lamp and
Standby lamp are
blinking alternately.
Indoor unit capacity is too low.
Indoor unit capacity is too high.
Check that the total capacities of the indoor and
outdoor units are appropriate.
P05
displayed
Timer lamp and
Standby lamp are
blinking alternately.
Reversed phase or open phase in the 3-phase
power at one of the outdoor units in the group.
Reverse 2 phases of the outdoor unit 3-phase power
and connect them correctly.
Fill up the gas appropriately.
Check that the indoor and outdoor unit types are correct.
Connect the indoor unit ceiling panel connector correctly.
Insufficient gas
P12
displayed
L02
displayed
L13
Check whether the fan holder is loose.
Check the wiring between the DC fan and the PCB.
DC fan trouble at one of the indoor units in the
group.
Ceiling panel connector at one of the indoor units
in the group is not connected correctly.
Indoor-outdoor unit type mismatch.
displayed
L07
Perform automatic address setting.
(See section “Automatic Address Setting” for Type K1
(for Link Wiring).)
L10
displayed
Both the Operation
lamp and Standby
lamp are blinking
together.
Check outdoor operation with separate maintenance-use remote controller.
Remote control communication wiring is connected
to the indoor unit, however it is set for individual
operation.
SM830231-02̲Single̲欧州.indb 317
SM830231-02̲Single̲欧州.indb 317
2014/09/19 13:21:50
2014/09/19 13:21:50
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...