1
1-402
Attach the heat exchanger
pipe thermistor in the middle
of each pass-line (pipe) in
the heat exchanger.
The thermistor is fixed
in band.
Then, it must not make
tension to the wire.
Cover the aluminum tape
with thermal insulation.
And also cover sensor
(copper portion) with
thermal insulation completely.
Installation
Thermistor for Liquid pipe and Heat exchanger pipe middle
Liquid pipe thermistor
Heat exchanger pipe thermistor
Attach the liquid pipe thermistor
to the liquid pipe located in the
lowest position after distributer
in heat exchanger.
Cover the thermistor
and pipe with
aluminum tape.
Cover the thermistor
and pipe with
aluminum tape.
Thermal insulation and
wiring are fixed in two
bands.
Cover the aluminum
tape with thermal
insulation.
Installation of Strainer (Field supplied)
Attach the strainer to the side of the outdoor unit for Gas & Liquid piping.
(See the “System Overview” on previous page.)
Attachment of NOTES Label (Supplied parts)
Please be sure to apply the NOTES label at the designated area of the outdoor unit when cutting a jumper
wire on the circuit board.
NOTES
SM830231-02̲Single̲欧州.indb 402
SM830231-02̲Single̲欧州.indb 402
2014/09/19 13:22:07
2014/09/19 13:22:07
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...