1
1-307
Indoor unit remote controller main-sub setting
When multiple wall mounted indoor units are installed for group control in a simultaneous-operation multi system,
set the control PCB at the No. 2 and following wall mounted units to “Sub remote control”.
If a wired remote controller is used, set the wired remote controller to “Sub”.
If 2 wireless remote controllers are used, set the wireless PCB (DIP switch) on the second remote controller to
“Sub”.
Indoor unit address setting
If multiple single-type units are installed in the same room, the addresses can be set to prevent signal interference.
By coordinating the numbers of the indoor unit (wireless PCB) and remote controller addresses, up to 6 indoor
units can be controlled independently by their respective remote controllers.
Independent control is not possible when a simultaneousoperation multi system is used.
Checking the addresses
Press the remote controller address button to display the current address on the remote controller display.
If this address matches the indoor unit (wireless PCB) address, the buzzer will sound.
(If ALL is set, the buzzer will always sound.)
If ALL is set, operation is possible regardless of the indoor unit address.
Point the remote controller toward the receiver (indoor unit) that you wish to operate, and send the operation
signal.
Remote controller address setting
Press and hold the address button for 4 seconds or longer to display the address on the remote controller display.
The current address starts blinking.
The address changes each time the remote controller address button is pressed: ALL → 1 → 2 → 3 → ... → 6.
Set the address to match the remote controller you wish to operate.
When the SET button is pressed, the address stops blinking and displays for 5 seconds.
The buzzer sounds if the address matches the indoor unit.
Remote
controller
address
display
Address
ALL
Address
1
Address
2
Address
3
Indoor unit
PCB address,
DIP switch
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
For address switches 1, 2, and 3, turn DIP switch 1 to OFF.
For address switches 4, 5, and 6, turn DIP switch 1 to ON.
Address switch
Test
Remote controller
Sub On
Main Off
1
2
3
ON
Indoor unit control PCB
2 HP
DIP switch
(SW101)
Address switch
(SW102)
3 HP
DIP switch
(SW101)
Address switch
(SW102)
SM830231-02̲Single̲欧州.indb 307
SM830231-02̲Single̲欧州.indb 307
2014/09/19 13:21:49
2014/09/19 13:21:49
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...