CAUTION
CAUTION
1. This unit requires no additional refrigerant charge up to tubing length 20 m (Type 50: 30 m).
In case of more than 20 m (Type 50: 30 m), additional refrigerant charge is required.
2. In case of multi type installation, indoor units should be installed within the same room.
If multi type indoor units are installed in different rooms, temperature control may develop problems
because thermostat operation must follow the thermostat condition of 1 indoor unit only (the main unit).
WARNING
Always check the gas density for the room in which the unit is installed.
Check of limit density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally
escapes, its density does not exceed the limit level.
If the density might exceed the limit level, it is necessary to set up an opening between it and the adjacent room,
or to install mechanical ventilation which is interlocked with the leak detector.
(Total refrigerant charged amount: k
g
)
(Min. indoor volume where indoor unit is installed: m
3
)
< Limit density 0.3 (k
g
/m
3
)
The limit density of refrigerant which is used in this unit is 0.3 k
g
/m
3
(ISO 5149).
The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount
that is charged at the field. (Refer to the unit’s nameplate for the amount of charged refrigerant at shipment.)
Minimum indoor volume & floor area relative to the amount
of refrigerant are roughly as given in the following table.
10
13.5
27.0
40.5
54.0
67.5
81.0
94.5
108
121.5
135
5
10
15
20
25
30
35
40
45
50
m
3
m
2
20
30
40k
g
Min. indoor floor area
(when the ceiling is 2.7 m high)
Range below the
density limit of
0.3 k
g
/m
3
(Countermeasures
not needed)
Range above
the density limit
of 0.3 k
g
/m
3
(Countermeasures
needed)
Min. indoor volume
Total amount of refrigerant
Pay special attention to any location, such as a basement or recessed area, etc. where leaked refrigerant
can collect, since refrigerant gas is heavier than air.
SM830231-02̲Single̲欧州.indb 278
SM830231-02̲Single̲欧州.indb 278
2014/09/19 13:21:46
2014/09/19 13:21:46
Содержание S-100PF1E5A
Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...
Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...
Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...
Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...