4-44
Note
Related page
• For parameters which No. have a suffix of “
*
”
, changed contents will be validated when
you turn on the control power.
• P.3-30... “Inputs and outputs on connector X4”
Pr5.06
Title
Sequence at Servo-Off
Related
control mode
P S T F
Range
0 to 9
Unit
—
Default
0
Caution
Related page
Specify the status during deceleration and after stop, after servo-off.
Setup
value
During deceleration
*
3
After stalling
Positional deviation/
feedback scale
deviation
0
Dynamic Brake (DB) action
Dynamic Brake (DB) action
Clear
*
4
1
Free-run (DB OFF)
Dynamic Brake (DB) action
Clear
*
4
2
Dynamic Brake (DB) action
Free-run (DB OFF)
Clear
*
4
3
Free-run (DB OFF)
Free-run (DB OFF)
Clear
*
4
4
Dynamic Brake (DB) action
Dynamic Brake (DB) action
Hold
*
2
5
Free-run (DB OFF)
Dynamic Brake (DB) action
Hold
*
2
6
Dynamic Brake (DB) action
Free-run (DB OFF)
Hold
*
2
7
Free-run (DB OFF)
Free-run (DB OFF)
Hold
*
2
8
Emergency stop
*
1
Dynamic Brake (DB) action
Clear
*
4
9
Emergency stop
*
1
Free-run (DB OFF)
Clear
*
4
*
1 Emergency stop refers to a controlled immediate stop with servo-on.
The torque command value is limited during this process by Pr5.11 Emergency stop torque setup.
*
2 If the positional command is kept applied or the motor is kept running with servo-off condition, positional
deviation is accumulated, causing Err24.0 Excess positional deviation protection to be issued. If
the servo is turned ON while the position or feedback scale is significantly deviating, the motor may
rapidly operate to reduce the deviation to 0. Remember these requirements if you want to maintain the
positional deviation/feedback scale deviation.
*
3 Deceleration period is the time required for the running motor to speed down to 30 r/min. Once the
motor speed drops below 30 r/min, it is treated as in stop state regardless of its speed.
*
4 Positional deviation/feedback scale deviation is always cleared to 0.
If an error occurs during servo-off, follow Pr5.10 Sequence at alarm. If the main power is
turned off during servo-off, follow Pr5.07 Sequence during main power interruption.
Refer to P.2-32, "Timing Chart"-Servo-ON/OFF action while the motor is at stall" of
Preparation as well.
Pr5.07
Title
Sequence at main power OFF
Related
control mode
P S T F
Range
0 to 9
Unit
—
Default
0
Caution
Specify the status during deceleration after main power interrupt or after stoppage.
The relationship between the setup value of Pr5.06 and the operation and process at
deviation counters is the same as that for Pr5.07 (sequence at main power OFF).
If an error occurs with the main power supply turned off, Pr5.10 Sequence at alarm is
applied to the operation.
When the main power supply is turned off with servo-on state, Err13.1 Main power
undervoltage error occurs if Pr5.08 LV trip selection with main power off = 1, and the
operation follows Pr5.10 Sequence at alarm.
1. Details of parameter
[Class 5] Enhancing setting
Содержание MINAS A5-series
Страница 36: ...1 24 MEMO ...
Страница 118: ...2 82 MEMO ...
Страница 168: ...3 50 MEMO ...
Страница 272: ...5 42 MEMO ...
Страница 351: ...7 55 1 Before Using the Products 2 Preparation 3 Connection 4 Setup 5 Adjustment 6 When in Trouble 7 Supplement MEMO ...
Страница 367: ...7 71 1 Before Using the Products 2 Preparation 3 Connection 4 Setup 5 Adjustment 6 When in Trouble 7 Supplement MEMO ...